Thermal Fire Detection Gains A Prescriptive Path

New UL 2684 listing for Teledyne FLIR Axx-Series thermal cameras, combined with NFPA 72 recognition, provides a standardized framework for specifying thermal image fire detection.

Thermal imaging has been identifying developing fire risks for years, but the absence of a dedicated product listing has limited its adoption in conventional fire alarm system designs. Recent changes to fire safety standards are helping address that challenge, creating a clearer path for engineers, integrators and fire protection professionals to specify thermal image fire detection.

The 2025 edition of NFPA 72, the National Fire Alarm and Signaling Code, introduced a dedicated section for thermal image fire detection under Section 17.12. It recognizes thermal image fire detectors as fire alarm initiating devices in their own right and requires them to be listed for that purpose.

While this was an important step toward broader adoption, code recognition and an independently listed product category are two different things.

Without a dedicated listing, specifying thermal detection typically required a performance-based justification, including design objectives, hazard analysis, modeling and approval from the authority having jurisdiction (AHJ). Each project required a separate evaluation, often without established precedents.

ANSI/CAN/UL 2684 addresses this challenge. Its first edition, published in June 2024, establishes testing and performance requirements for video and thermal image detectors used in fire alarm systems. It provides the independent benchmark that thermal image fire detection has lacked.

Teledyne FLIR’s Axx-Series thermal cameras are the first thermal imagers listed to UL 2684.

What Changes At Submission

The authority having jurisdiction (AHJ) retains final approval responsibility. However, the documentation and technical basis presented for review have changed.

Previously, designers often had to develop a project-specific performance-based justification. With a listed detector, they now have a prescriptive pathway based on a code-recognized device evaluated by an accredited third-party laboratory against a consensus standard.

For design firms, this provides a repeatable starting point rather than requiring a new technical justification for every project.

The extent to which this shortens approval timelines will depend on individual jurisdictions, and several design cycles will be needed to establish its broader impact. Nevertheless, plan reviews can now begin with a published testing and performance benchmark.

The change also benefits system integrators. Early fire detection has traditionally been a specialized offering, often requiring consultants to support project approvals. A listed detector could help bring thermal fire detection into more conventional fire alarm procurement and submittal processes.

The Detection Window

Fire rarely develops without warning. Many electrical and industrial failures generate heat signatures well before visible damage or combustion occurs.

For example, a high-resistance connection in a motor control center can become progressively warmer for hours before anything begins to scorch. Switchgear can also develop abnormal thermal signatures well ahead of an arc event.

Conventional fire detection systems generally respond to products of combustion, including smoke and flame, or heat reaching a detector. By that stage, the fire process may already be underway.

Radiometric thermal imaging can identify the heat that precedes these conditions.

Teledyne FLIR Early Fire Detection (EFD) solutions use UL 2684-listed FLIR A40, A50 and A70 Axx-Series thermal cameras to measure the temperature of every pixel in a scene multiple times per second across defined regions of interest.

Alarms can be configured using absolute temperature thresholds, temperature differences between regions and rate-of-rise measurements. This allows the system to respond to changing thermal conditions rather than simply detecting whether an object has reached a particular temperature.

That distinction helps reduce nuisance alarms. Equipment that consistently operates at an elevated temperature does not necessarily indicate a fire risk. However, the same equipment showing a steady temperature increase over a shift could indicate a developing problem.

The warning time depends on the nature of the failure. A deep-seated fire in stored materials may develop over several hours, while thermal runaway in a battery cell can progress much faster once initiated. In many situations, however, abnormal heating can provide an opportunity to intervene before a more serious event develops.

Where It Belongs In A Design

Thermal imaging is not intended to replace conventional area smoke detection and should not be specified as a substitute.

Because thermal imaging is line-of-sight technology, it monitors only the areas covered by the camera. This makes it particularly suitable for defined risk zones, including confined switchgear rooms and large storage facilities, with camera optics selected to match the environment.

When cameras include an integrated visible-light camera, thermal detection can be combined with visual verification. An alarm can provide both thermal and visible video of the scene at the moment it is triggered.

This gives operators additional context to assess an event and make informed response decisions, rather than dispatching personnel based solely on an unexplained alarm.

The Part Owners Care About

Although design engineers do not always make the financial case for fire detection systems, the potential economic benefits are important to building owners and operators.

Property insurers assess potential losses based partly on how quickly a fire can be detected and controlled. Detection timing directly influences the potential extent of property damage, downtime and replacement costs.

Teledyne FLIR estimates that thermal detection can protect approximately $100 in asset value, downtime and replacement costs for every $1 invested in the technology.

This provides a financial argument that building owners and their insurers can consider when evaluating early fire detection investments.

“We’ve had customers running this for years, and the feedback was always the same. They believed in the capability; getting it through plan review was the hard part. That’s what the listing changes. Engineers and AHJs have a benchmark to work from rather than assessing each project from scratch,”

said Matthew Hasty, Global Vertical Director for Science, Automation, and Early Fire Detection at Teledyne FLIR.

The 2025 edition of NFPA 72 recognized the device category, and products are now listed to the corresponding UL 2684 standard.

Whether these developments will change specification practices across the industry remains to be seen. However, the conversation is shifting toward adoption rather than whether thermal imaging technology can be approved for fire detection applications.

Teledyne FLIR, a subsidiary of Teledyne Technologies, is a global provider of intelligent sensing solutions for defense and industrial applications. Founded in 1978, the company develops thermal imaging, visible-light imaging, video analytics, measurement and diagnostic technologies, and advanced threat detection systems for industrial, commercial, public safety and defense markets.

Internal Links URLs:

https://security.world/category/video-surveillance

External Links URLs:

https://www.flir.com


Frequently Asked Questions (FAQs)

1. What is UL 2684?

ANSI/CAN/UL 2684 is a standard establishing testing and performance requirements for video and thermal image detectors used in fire alarm systems.

2. What does NFPA 72 Section 17.12 address?

The 2025 edition of NFPA 72 introduced a dedicated section recognizing thermal image fire detectors as fire alarm initiating devices.

3. Which Teledyne FLIR cameras are listed to UL 2684?

The FLIR A40, A50 and A70 thermal cameras in the Axx-Series are the first thermal imagers listed to UL 2684.

4. How does thermal imaging detect developing fires?

Radiometric thermal cameras measure temperature across individual pixels and identify abnormal heating using temperature thresholds, differences between regions and rate-of-rise measurements.

5. Can thermal imaging replace conventional smoke detectors?

No. Thermal imaging is intended to complement conventional fire detection systems and provide additional monitoring in defined high-risk areas.

6. What are the benefits of thermal fire detection for industrial facilities?

It can identify abnormal heating before smoke or flames develop, providing additional time to investigate potential hazards and take preventive action.

Source: flir.com
0 Comments